Ord 670
ORDINANCE NO. 670
AN ORDINANCE OF THE CITY OF POWAY, CALIFORNIA, RESCINDING CHAPTER
15.24 OF THE POWAY MUNICIPAL CODE AND ADOPTING NEW CHAPTER 15.24
REGARDING THE POWAY FIRE CODE, WHICH ADOPTS BY REFERENCE THE
CALIFORNIA FIRE CODE, 2007 EDITION, AND INTERNATIONAL FIRE CODE, 2006
EDITION, WITH CERTAIN AMENDMENTS, ADDITIONS AND DELETIONS
WHEREAS, Chapter 15.24 of the Poway Municipal Code is the Poway Fire
Code, which adopts by reference the California Uniform Fire Code; and
WHEREAS, Chapter 15.24 currently adopts by reference the 2001 version of the
California Uniform Fire Code; and
WHEREAS, there is a need to replace Chapter 15.24 because the State of
California has recently adopted a 2007 version of the California Fire Code; and
WHEREAS, Sections 50022.1 through 50022.10, inclusive, of the Government
Code, provide authority for the adoption by reference of Codes, or portion of such
Codes; and
WHEREAS, the City of Poway is mandated by the Health and Safety Code to
adopt the same requirements as set forth in the State's regulations, adopted pursuant to
Health and Safety Code section 17922, and the same requirements as set forth in the
2007 California Fire Code, hereinafter referred to collectively as the Fire Code or
Codes; and
WHEREAS, Code amendments adopted by the State of California shall take
precedence over the 2007 California Fire Code language. The 2007 California Fire
Code language shall be used for those Code sections not adopted by the State; and
WHEREAS, local amendments adopted by the City of Poway shall take
precedence over 2007 California Fire Code; and
WHEREAS, Health and Safety Code section 17958.5 permits the City of Poway
to make such changes or modifications to the Codes as are reasonably necessary
because of local conditions; and
WHEREAS, Health and Safety Code section 17958.7 requires that the City of
Poway, before making any changes or modifications pursuant to section 17958.5, make
express findings that such changes or modifications are needed due to climatic,
geographic, or topographic conditions; and
-
Ordinance 670
Page 2
WHEREAS, the City Council of the City of Poway finds that the City of Poway
has certain climatic, geologic, and topographical features that can have a deleterious
effect on emergency services such as fire protection and emergency medical services;
and
WHEREAS, the City Council of the City of Poway finds that the modifications and
changes to the 2007 California Fire Code are reasonably necessary because of the
local climatic, geological, and topographical conditions identified in Attachment A; and
WHEREAS, certain amendments to the 2007 California Fire Code are necessary
to mitigate said deleterious effects to the extent possible.
NOW THEREFORE, the Poway City Council does ordain as follows:
SECTION 1. Poway Municipal Code Chapter 15.24 is hereby rescinded, and a
new Chapter 15.24 is added in its place as follows:
15.24.010 Adoption of California Fire Code
The City of Poway adopts by reference the 2007 California Fire Code, including
Appendix Chapters 1 and 4, and Appendices B, F, and H, as published by the
International Code Council, except those portions that are deleted, modified, or
amended by this chapter. One copy of the above-mentioned Code has been, and is
now filed, in the office of the City Clerk or the Fire Marshal, City of Poway, and the same
is adopted and incorporated as fully as if set out at length herein. From the effective
date of the ordinance codified in this chapter, the provisions thereof shall be controlling
within the limits of the City of Poway.
15.24.020 Definitions.
The following definitions are added to section 202:
Administrator. Wherever the term "Administrator" is used in the California Fire
Code, it means the Poway City Council.
Bureau of fire prevention. Wherever the term "Bureau of fire prevention" is used,
it means "Fire Prevention Division."
Chief of the bureau of fire prevention. Wherever the term "Chief of the bureau of
fire prevention" is used, it means "Fire Marshal."
Corporation Counsel. Wherever the term "Corporation Counsel is used, it means
the City Attorney for the City of Poway.
Ordinance 670
Page 3
Fire Department. Any regularly organized fire department regularly charged with
the responsibility of providing fire protection to the jurisdiction.
Fire Authority Having Jurisdiction (FAHJ). The designated entity providing
enforcement of fire regulations as they relate to planning, construction, and
development. This entity for the City of Poway also provides fire suppression and other
emergency services.
Fire Hazard. Anything that increases or could cause an increase of the hazard
or menace of fire to a greater degree than customarily recognized as normal by persons
in the public service regularly engaged in preventing, suppressing, or extinguishing fire,
or any thing or act, which could obstruct, delay, hinder, or interfere with the operations
of the fire department or egress of occupants in the event of fire.
Ignition-Resistant Material. Any product which, when tested in accordance with
ASTM E84 for a period of 30 minutes, shall have a flame spread rating of not over 25 and
show no evidence of progressive combustion. In addition, the flame front shall not
progress more than 10-1/2 feet beyond the centerline of the burner at any time during the
test.
Materials shall pass the accelerated weathering test and be identified as Exterior
type, in accordance with ASTM D 2898 and ASTM D 3201. All materials shall bear
identification showing the fire performance rating thereof. That identification shall be
issued by ICC-ES or a testing facility recognized by the State Fire Marshal having a
service for inspection of materials at the factory.
Fire-Retardant-Treated Wood or noncombustible materials as defined in section
202 shall satisfy the intent of this section.
The enforcing agency may use other definitions of ignition-resistant material that
reflect wildfire exposure to building materials and/or their materials performance in
resisting ignition.
Jurisdiction. Wherever this term is used in the California Fire Code, it means the
jurisdictional boundaries of the City of Poway.
Public Nuisance. Any condition declared by this Code or the Chief to be a fire or
health hazard.
Response Time. Response time is used in the Fire Code portion of the California
Building Standards Code; it means the time period from when the original incident alarm
was received by dispatch to when the first fire unit arrives on scene.
Ordinance 670
Page 4
Wildland-Urban Interface Code. The Code regulating and governing the
mitigation of hazard to life and property from the intrusion of fire from wildland
exposures, fire from adjacent structures and prevention of structure fires from spreading
to wildland fuels as adopted by the local FAHJ.
Whenever the terms "This Code" and ".2006 International Fire Code" are used,
they shall mean the 2007 California Fire Code as modified by the City of Poway with the
deletions, revisions, and additions set forth in the amendments.
The definition of "High-Rise Building" in section 202 is modified to read as
follows:
High-Rise Building.
1. "Existing high-rise structure" means a high-rise structure, the construction of
which is commenced or completed prior to July 1, 1974.
2. "High-rise structure" means every building of any type of construction or
occupancy having floors used for human occupancy located more than 55 feet
above the lowest floor level having building access (see California Building Code,
section 403.1.2), except buildings used as hospitals as defined in Health and
Safety Code section 1250.
3. "New high-rise structure" means a high-rise structure, the construction of which is
commenced on or after July 1, 1974.
The definition of "High-hazard Group H" - under "occupancy classification" in section
202 is modified to read as follows:
High-hazard Group H. High-hazard Group H occupancy includes, but is not
limited to, the use of a building or structure, or a portion thereof that involves the
manufacturing, processing, generation or storage of materials that constitute a physical
or health hazard in quantities in excess of quantities allowed in control areas
constructed and located as required in section 2703.8.3. Hazardous uses are classified
in Groups H-1, H-2, H-3, H-4, and H-5 and shall be in accordance with this Code and
the requirements of section 415 of the California Building Code.
Ordinance 670
Page 5
Exceptions. The following shall not be classified in Group H, but shall be
classified in the occupancy that they most nearly resemble.
1 Buildings and structures that contain not more than the maximum allowable
quantities per control area of hazardous materials as shown in Tables 2703 1 1 (1) and
2703 1 1 (2), provided that such buildings are maintained in accordance with this Code.
2. Buildings utilizing control areas in accordance with section 27038 3 that
contain not more than the maximum allowable quantities per control area of hazardous
materials as shown in Tables 2703 1 1 (1) and 2703 1 1 (2).
3 Wholesale and retail sales and storage of flammable and combustible liquids
in mercantile occupancies conforming to Chapter 34
4 Closed piping systems containing flammable or combustible liquids or gases
utilized for the operation of machinery or equipment.
5 Cleaning establishments that utilize combustible liquid solvents having a flash
point of 1400F (60oC) or higher in closed systems employing equipment listed by an
approved testing agency, provided that this occupancy is separated from all other areas
of the building by 1-hour fire barriers constructed in accordance with section 706 of the
International Building Code or 1-hour horizontal assemblies constructed in accordance
with section 711 of the International Building Code, or both.
6 Cleaning establishments that utilize a liquid solvent having a flash pOint at or
above 2000F (93OC).
7 Liquor stores and distributors without bulk storage.
8 Refrigeration systems.
9 The storage or utilization of materials for agricultural purposes on the
premises.
10 Stationary batteries utilized for facility emergency power, uninterrupted power
supply or telecommunication facilities, provided that the batteries are provided with
safety venting caps and ventilation is provided in accordance with the International
Mechanical Code.
11 Corrosives shall not include personal or household products in their original
packaging used in retail display or commonly used building materials.
Ordinance 670
Page 6
12. Display and storage of nonflammable solid and nonflammable or
noncombustible liquid hazardous materials in quantities not exceeding the maximum
allowable quantity per control area in Group M or S occupancies complying with section
2703.8.3.5.
13. The storage of black powder, smokeless propellant, and small arms primers
in Groups M and R-3, and special industrial explosive devices in Groups B, F, M, and S,
provided such storage conforms to the quantity limits and requirements of this Code.
15.24.030 General Precautions Against Fire
Section 307.4.1 is modified to read as follows:
307.4.1 Bonfires. Bonfires are prohibited within the City of Poway.
Section 307.4.2.1 is added as follows:
307.4.2.1 Recreational fires comprised of ordinary combustibles such as wood
and paper products are prohibited in high and very high fire severity zones as
geographically defined by the Wildland-Urban Interface Code. The Chief may authorize
the use of gas fired, non-spark generating recreational fires in accordance with section
307 for recreational purposes only.
Section 307.5.1 is added as follows:
307.5.1 An adult must be present at all times to watch and tend to outdoor fires.
Section 316 is added as follows:
316 General Storage of Firewood. Firewood shall not be stored in unenclosed
spaces beneath buildings or structures, or on decks or under eaves, canopies or
other projections or overhangs. When required by the Code official, storage of
firewood material stored in the defensible space shall be located a minimum of 30
feet from structures and separated from the crown of trees by a minimum of 15
feet, measured horizontally. Firewood and combustible materials not for
consumption on the premises shall be stored so as to not pose a hazard.
15.24.040 Fire and Evacuation Drill Frequency and Participation
Ordinance 670
Page 7
Footnote "a" to Table 405.2 is modified to read as follows:
a) The frequency of evacuation drills in all school levels may be modified in
accordance with section 408.3.2. Secondary level schools need only conduct
evacuation drills twice each school year.
15.24.050 Fire Service Features
Section 502 is modified to add a definition of "Fire Access Road" as follows:
Fire Access Road. This is a general term inclusive of all other terms such as
driveway, fire lane, public street, private street, parking lot, lane, and access roadway.
Section 503.1.2 is modified to read as follows:
503.1.2 Additional Access. The Chief may require one or more secondary
means of access to a project, development or area where he or she deems that such
access is necessary for emergency operations and/or evacuation. The maximum length
of a dead-end road, including all dead-end roads accessed from that dead-end road,
shall not exceed the following cumulative lengths, regardless of the number of parcels
served:
Parcels zoned for less than 1 acre 800 feet
Parcels zoned for 1 acre to 4.99 acres 1,320 feet
Parcels zoned for 5 acres to 19.99 acres 2,640 feet
Parcels zoned for 20 acres or larger 5,280 feet
These requirements may be modified when, in the opinion of the Chief,
conditions warrant.
All lengths shall be measured from the edge of the roadway surface at the
intersection that begins the road to the end of the road surface at its farthest point.
Where a dead-end road crosses areas of differing zoned parcel sizes, requiring different
length limits, the shortest allowable length shall apply.
Secondary access must be remote from the primary access, and must meet all
provisions of this section.
Ordinance 670
Page 8
Section 503.2.1 is modified to read as follows:
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed
improved width of not less than 20 feet, except that single-family residential driveways
serving no more than two improved parcels containing dwelling units, shall have a
minimum of 16 feet of unobstructed improved width. In most cases, the City of Poway
construction standards for streets (PMC Chapter 12.20) will be more restrictive. The
more restrictive standard shall apply. Vertical overhead clearance shall be a minimum
13 feet, 6 inches.
Exceptions:
1. Upon approval by the Chief, vertical clearances or width may be reduced,
provided such reduction does not impair access by fire apparatus and approved signs
are installed and maintained indicating the established vertical clearance.
2. Fire access roadways, gated entrances with card readers, guard stations or
center medians, which have separated lanes of one-way traffic, shall be not less than
12 feet wide per lane.
Sections 503.2.3 through 503.2.5 are modified to read as follows:
503.2.3 Surface. Fire apparatus access roads shall be designed and
maintained to support the imposed loads of fire apparatus not less than 75,000 Ibs.
unless authorized by the FAHJ, and shall be provided with an approved paved surface
so as to provide all-weather driving capabilities. When deemed necessary in the opinion
of the Chief, a paved driving surface shall mean asphalt or concrete surface.
503.2.4 Turning Radius. The turning radius of a fire apparatus access road
shall be a minimum of 28 feet as measured to the inside edge of the improvement width
or as approved by the Chief.
503.2.5 Dead Ends. All dead-end fire access roads in excess of 150 feet in
length shall be provided with approved provisions for the turning around of emergency
apparatus. A cul-de-sac shall be provided in residential areas where the access
roadway serves more than two structures. Minimum unobstructed paved radius width
for a cul-de-sac shall be 38 feet in residential areas. The Fire Chief shall establish a
policy identifying acceptable turnarounds for various project types.
Ordinance 670
Page 9
Section 503.2.7 is modified to read as follows:
503.2.7 Grade. The gradient for a fire apparatus access roadway shall not
exceed 20.0 percent. Grades exceeding 15.0 percent (incline or decline) shall not be
permitted without mitigation. Mitigation shall consist of, at a minimum, the installation of
fire sprinkler systems and a surface of Portland cement concrete (PCC), with a deep
broom finish perpendicular to the direction of travel, or equivalent, to enhance traction.
The Chief may require additional mitigation measures where he or she deems appropriate.
The angle of departure and angle of approach of a fire access roadway shall not exceed 7
degrees (12 percent) or as approved by the Chief.
Section 503.3.1 is added as follows:
503.3.1 Marking of Fire Apparatus Access Roads. When required, approved
signs or other approved notices shall be provided and maintained for fire apparatus
access roads to identify such roads and prohibit the obstruction thereof or both.
All new public roads, all private roads within major subdivisions, and all private
road easements serving four or more parcels shall be named. Road name signs shall
comply with City of Poway construction details and materials for porcelain street name
signs P9FL. The Chief may require the posting of a fire access roadway where parking
has obstructed or could obstruct the required width.
Section 503.4.1 is added as follows:
503.4.1 Roadway Design Features. Roadway design features (including speed
bumps, speed humps, and speed control dips) that may interfere with emergency
apparatus responses shall not be installed on fire access roadways, unless they meet
design criteria approved by the Chief.
Section 503.6.1 is added as follows:
503.6.1 Security Gates. All gates or other structures or devices which could
obstruct fire access roadways or otherwise hinder emergency operations are prohibited
unless they meet standards approved by the Chief, and receive Specific Plan approval.
All automatic gates across fire access roadways and driveways shall be
equipped with approved emergency key-operated switches overriding all command
functions and opening the gate(s). Gates accessing more than four residences or
residential lots, or gates accessing hazardous institutional, educational or assembly
occupancy group structures, shall also be equipped with approved emergency traffic
Ordinance 670
Page 10
control-activating strobe light sensor(s), or other devices approved by the Chief, which
will activate the gate on the approach of emergency apparatus with a battery back-up or
manual mechanical disconnect in case of power failure. In the event of a power failure,
the gate shall be automatically transferred to a fail-safe mode allowing the gate to be
manually pushed open without the use of special knowledge or equipment.
All automatic gates must meet fire department policies deemed necessary by the
Chief for rapid, reliable access.
Automatic gates serving more than one dwelling or residential lot in existence at
the time of adoption of this Ordinance are required to install an approved emergency
key-operated switch, or other mechanism approved by the Chief, at an approved
location, which overrides all command functions and opens the gate(s). Property
owners must comply with this requirement within 90 days of written notice to comply.
Where this section requires an approved key-operated switch, it shall be dual
keyed or dual switches provided to facilitate access by law enforcement personnel.
Section 505.1 is modified to read as follows:
505.1 Address Numbers. Approved numbers and/or addresses shall be placed on
all new and existing buildings and at appropriate additional locations as to be plainly visible
and legible from the street or roadway fronting the property from either direction of
approach. Said numbers shall contrast with their background, and shall meet the following
minimum standards as to size: four inches (4") for single-family dwellings; six inches (6")
for multi-family dwellings; between six inches (6") minimum and eighteen inches (18")
maximum for commercial buildings; and between eighteen inches (18") minimum and
twenty-four inches (24") maximum for industrial buildings. Additional numbers shall be
required where deemed necessary by the Fire Marshal, such as rear access doors,
building corners, and entrances to commercial centers. The Fire Chief may establish
different minimum sizes for numbers for various categories of projects.
Roof numbers. When required by the Chief, roof numbers shall be installed
meeting current fire department standards deemed necessary by the Chief.
Section 505.3 is added as follows:
505.3 Easement Address Signs. All easements which are not named differently
from the roadway, from which they originate, shall have an address sign installed and
maintained, listing all street numbers occurring on that easement, located where the
easement intersects the named roadway. Minimum size of numbers on that sign shall
be four inches (4") in height with a minimum stroke of 3/8 inch, and shall contrast with
the background.
Ordinance 670
Page 11
Section 505.4 is added as follows:
505.4 Map/Directory. A lighted directory map, meeting current fire department
standards, shall be installed at each driveway entrance to multiple unit residential
projects and mobile home parks, where the number of units in such projects exceeds
15.
Section 505.5 is added as follows:
505.5 Response Map Updates. Any new development, which necessitates
updating of emergency response maps by virtue of new structures, hydrants, roadways
or similar features, shall be required to provide map updates in a format (PDF and/or
CAD format as approved by the FAHJ) or compatible with current department mapping
services, and shall be charged a reasonable fee for updating all response maps.
Section 506.1 is modified to read as follows:
506.1 Key Boxes. When access to or within a structure or an area is unduly
difficult because of secured openings or where immediate access is necessary for life
saving or firefighting purposes, the Chief is authorized to require a key box to be
installed in an accessible location. The key box shall be a type approved by the Chief
and shall contain keys to gain necessary access as required by the Chief.
Section 506.2.1 is added as follows:
506.2.1 Emergency Key Access. All central station-monitored fire detection
systems and fire sprinkler systems shall have an approved emergency key access box
on site in an approved location. The owner or occupant shall provide and maintain
current keys for the structure(s) for fire department placement in the box, and shall
notify the fire department in writing when the building is re-keyed.
Section 507.3 is modified to read as follows:
507.3 Penalties. The penalties set forth in the California Penal Code shall be
applicable to violations of section 507 - Hazards to Firefighters.
Section 508.2.2 is modified to read as follows:
508.2.2 Water Storage Tanks. Water storage tanks, when permitted by the Chief,
shall comply with Table No. 508.2.2.
Ordinance 670
Page 12
TABLE NO. 508.2.2
Gallons Per Minute Capacity Duration
Building Square Feet Water Flow Gallons Minutes
Up to 3,600 10,000 40
3,601 to 7,700 250 15,000 60
7,701 and above 333 20,000 60
When exposure distance is one hundred feet (100') or less from adjacent property or the
severity of potential fire risk has been determined to exist, an increase in water storage
may be required by the Chief.
1. Tank elevation shall be equal to or higher than the Fire Department
connection on the premises. Regardless of domestic use, all tanks shall be equipped
with a device that will ensure that the tank contains the designated amount of water for
fire flow duration as determined by the Fire Department. Tank size may be increased to
serve multiple structures on a single parcel.
2. Supply outlet shall be at least 4 inches in diameter from the base of the tank
to the point of outlet at the Fire Department connection. The Fire Department connection
shall be at least one 4-inch National Standard Thread (male), reduce to one 2-1/2-inch
National Standard Thread (male). Additional outlets may be required.
3. Location of Fire Department outlet to be determined on the plot plan when
submitted to the Fire Department. Consideration will be given to factors such as
topography, elevations, and distance from structures, driveway access, and prevailing
winds.
4. The outlet shall be located along an access roadway and shall not be closer
than 50 feet or further than 150 feet from the structure.
5. All exposed tank supply pipes shall be of an alloy or other material listed for
above ground use. Adequate support shall be provided.
6. Water storage tanks shall be constructed from materials approved by the Fire
Marshal and installed per manufacturer recommendations.
7. The Chief may require any necessary information to be submitted on a plot
plan for approval.
8. Vessels previously used for products other than water shall not be permitted.
Ordinance 670
Page 13
Section 508.3 is modified to read as follows:
508.3 Fire Flow Requirements. Fire flows shall be based on Appendix B.
Consideration should be given to increasing the gallons per minute set forth in Appendix
B to protect structures of extremely large square footage and for such reasons as: poor
access roads; grade and canyon rims; hazardous brush; and response times greater
than five minutes by a recognized fire department or fire suppression company.
In hazardous fire areas as defined in Appendix B, the main capacity for new
subdivisions shall not be less than 8 inches in diameter and capable of supplying the
required fire flow, with a maximum flow velocity of 15 feet per second, unless otherwise
approved by the Chief and the City Engineer.
If fire flow increases are not feasible, the Chief may require alternative design
standards such as: alternative types of construction providing a higher level of fire
resistance; fuel break requirements which could include required irrigation; modified
access road requirements; specified setback distances for building sites addressing
canyon rim developments and hazardous brush areas; and other requirements
authorized by this Code and as specified by the Chief.
Section 508.5.1 is modified to read as follows:
508.5.1 Required Installations. The location, type and number of fire hydrants
connected to a water supply capable of delivering the required fire flow shall be
provided on the public or private street, or on the site of the premises to be protected, or
both, as required and approved by the Fire Code Official. Fire hydrants shall be
accessible to the Fire Department apparatus by roads meeting the requirements of
section 503. For fire safety during the construction, alteration, or demolition of a
building, see section 1412.1.
Section 508.5.1.1 is added as follows:
508.5.1.1 Water Supplies and Fire Hydrants. For Group R-3 and U
Occupancies, an approved water supply capable of supplying the required fire flow for
fire protection shall be provided to all premises upon which facilities, buildings or
portions of buildings are hereafter constructed or moved into or within the jurisdiction.
When any portion of the facility or building protected is in excess of 500 feet for a parcel
sized one acre or larger, or 350 feet for a parcel sized less than one acre from a water
supply on a public street, as measured by an approved route around the exterior of the
facility or building, on-site fire hydrants and mains capable of supplying the required flow
shall be provided when required by the Chief.
Ordinance 670
Page 14
Exception: Remodels and additions. Existing structures which are remodeled or
added to where the amount of new area does not exceed 1,500 square feet and the
additional or remodeled area is protected with an approved automatic fire extinguishing
system.
Section 508.5.1.1.2 is added as follows:
508.5.1.1.2 Fire Hydrant Systems - Placement. In multi-family zones and in
commercial and industrial zones, fire hydrants shall be installed at intersections, at the
beginning radius of cul-de-sacs, and every 300 feet of fire access roadways, regardless
of parcel size.
Exception: When improved methods of fire protection are provided, beyond
those required by the Code, and accepted by the Chief, adjusted spacing of fire
hydrants from those set forth above may be considered.
Section 508.5.1.1.3 is added as follows:
508.5.1.1.3 Fire Hydrant Systems - Materials/Construction. All fire hydrants
shall be of bronze construction, including all internal parts except seats. Alternate
materials may be used if approved by the Fire Marshal and the Public Works
Department. The stems shall be designed and installed in a manner that will ensure
that they will not be projected outward from the main body by internal water pressure
due to disassembly. The number and size of fire hydrant outlets shall be as follows:
1. One 4 inch and one 2-12 inch NST outlet. (4",2-12")
2. One 4 inch and two 2-12 inch NST outlets. (4", 2-12",2-12")
3. Two 4 inch and two 2-12 inch NST outlets. (4", 4", 2-12", 2-12")
In some instances the Chief may require the fire hydrant(s) to have any other
combination of 4 inch and 2-% inch outlets.
15.24.060 Building Services and Systems
Section 603.8.1 is modified to read as follows:
603.8.1 Residential Incinerators. Residential incinerators shall be prohibited.
Ordinance 670
Page 15
15.24.070 Fire Sprinklers Systems
Section 903.1.2 is added as follows:
903.1.2 Life Safety Sprinkler System. Life safety sprinkler systems shall meet
National Fire Protection Association Standards 13-D or 13-R, and City of Poway
installation policies as appropriate.
Section 903.2 is modified to read as follows:
903.2 Where Required. Approved automatic sprinkler systems in new buildings
and structures shall be provided in the locations described in this section. For the
purpose of fire-sprinkler systems, buildings separated by less than 10 feet from adjacent
buildings shall be considered as one building. Fire barriers, partitions and walls,
regardless of rating, shall not be considered as creating separate buildings for purposes of
determining fire sprinkler requirements. Mezzanines shall be included in the total square
footage calculation.
All occupancies within the City of Poway:
Commercial Residential (R3) Additions- Additions-
Commercial Residential
All buildings greater As Mitigation Additions of more than 50% increase or
than 5,000 sq. ft. twenty-five percent exceeding fire flow
(25%) of the square as defined in
footage of an existing
building, which results in Appendix "8"
a structure of 5,000
square feet or more,
shall be requ ired to be
protected throughout
the entire structure with
a sprinkler system
consistent with this
section.
Exceptions:
1. Commercial buildings built on a property line other than a public way shall be
protected by a fire sprinkler system consistent with the foregoing standards, regardless
of size. When present, utility easement(s) may be considered as building separation
distance when that utility easement will prevent construction of a structure within the
boundaries of that specific easement.
Ordinance 670
Page 16
2. Where an existing building or structure is not protected by an automatic fire
extinguishing system, but otherwise would be required to be protected if built as a new
building, its use will be allowed to continue until such time as any structural change
takes place which modifies, alters, or affects any bearing wall or similar structural
assembly at which time it shall be made to conform to the provisions of this Code.
3. Agricultural buildings constructed of wood or metal frames over which fabric or
similar material is stretched which are specifically used as green houses are exempt
from fire sprinkler. Requirements unless physically connected to other structures
4. When the required fire flow exceeds 1,500 gallons per minute as determined by
the provisions in Appendix B of this code, or when calculated according to the standard
published by the Insurance Services Office document entitled "Guide for Determination
of Required Fire F/ow." Sprinklers may be required as mitigation measures as set forth
by the Division of fire prevention residential sprinkler standards and as defined
elsewhere in the code. Sprinklers may be omitted from detached garages and carports.
A garage that is part of the building shall protect sprinkler heads against mechanical
damage with approved guards. Fire alarm signal shall be provided by a water flow
switch located on the sprinkler riser and the alarm bell(s) or other audible device shall
be of sufficient intensity to be clearly audible in all bedrooms. Water meters shall be a
minimum one-inch (1 "), and the water line from the meter to the building shall be a
minimum of one-inch (1 "). The system shall be subject to a test witnessed by the fire
agency and include the following: Static pressure of fifty (50) psi, but not less than two
hundred (200) psi.
Section 903.3.1 is modified to read as follows:
903.3.1 Standards. Sprinkler systems shall be designed and installed in
accordance with sections 903.3.1.1, 903.3.1.2 or 903.3.1.3.
For all sprinkler systems:
a) Required automatic fire extinguishing systems plans shall be approved by the
Fire Chief or his/her designee.
b) Plans shall be submitted prior to any installation commencing by a licensed
system designer and/or installer. Plans shall be approved prior to the beginning
of installation. Plans shall show all necessary engineering features and
calculations to document compliance with and as required by NFPA 13, 13R, and
13D.
Ordinance 670
Page 17
c) Standard test during and after installation shall be required as by NFPA 13, 13R,
and 13D, and fire prevention bureau standards. These tests must be performed
and documented prior to final inspection.
d) No building hereafter required to have an automatic fire extinguishing system
installed shall pass final building inspection or be issued a certificate of
occupancy until the fire extinguishing system passes final fire inspection.
e) If the Fire Prevention Division needs specialized consultant assistance for plan
checks, or if extensive inspections/re-inspections are required during installation,
a reasonable fee shall be charged to cover expenses. Fees shall be established
by resolution of the City Council.
f) For commercial and industrial occupancies commonly referred to as "spec
buildings" wherein no specific end use is identified at the time of plan check, the
sprinkler system shall provide a density of .45 gallons per minute/square foot for
a 3,000 square foot design area.
Section 903.4, Exception 1, is modified to read as follows:
903.4 Sprinkler System Monitoring and Alarms.
Exception 1 - Automatic sprinkler systems with less than 100 fire sprinklers
protecting one- and two-family dwellings.
Section 907.2.10.2 is modified to read as follows:
907.2.10.2 Power Source. In new construction and in newly classified Group R-
3.1 occupancies, required smoke alarms shall receive their primary power from the
building wiring when such wiring is served from a commercial source and shall be
equipped with a battery backup. Smoke alarms shall emit a signal when the batteries
are low. Wiring shall be permanent and without a disconnecting switch other than those
required for overcurrent protection. Smoke alarms may be solely battery operated when
installed in existing buildings; or in buildings without commercial power; or in buildings,
which undergo alterations, repairs or additions regulated by section 907.2.10.6.
Section 907.2.10.6 is added as follows:
907.2.10.6 Additions, Alterations or Repairs to Group R Occupancies. When the
valuation of an addition, alteration or repair to Group R occupancy exceeds $1,000 and
a permit is required, or when one or more sleeping rooms are added or created in
existing Group R occupancies, smoke alarms shall be installed in accordance with
section 907.2.10.
Ordinance 670
Page 18
15.24.080 Fuel Modification or Vegetation Modification
Section 1418 is added as follows:
1418. Fuel Modification or Vegetation Modification. Fuel modification or
vegetation modification shall be maintained prior to combustibles arriving on site.
15.24.090 Flammable Finishes
Section 1504.3.3.2 is added as follows:
1504.3.3.2 Spraying Space. Spray operations of flammable finishes are
prohibited outside if the spray area exceeds nine square feet and/or produce vapors
that could reach any source of ignition.
15.24.100 Storage and Processing of Wood Chips, Hogged Materials Fines,
Compost and Raw Product in Association With Yard Waste And Recycling Facilities
Section 1908.1 is modified to read as follows:
1908.1 General. The storage and processing (mulching, composting) of wood
chips, hogged materials, fines, compost and raw product produced from yard waste,
debris and recycling facilities shall be in accordance with section 1908.
Section 1908.1.2 is added as follows:
1908.1.2 Definitions. For the purpose of section 1908, certain words and
phrases are defined and certain provisions shall be construed as set forth herein, unless
it is apparent from the context that a different meaning is intended.
Aerated Static Pile means a composting process that uses an air distribution
system to either blow or draw air through the pile. Little or no pile agitation or turning is
performed.
Chipping and Grinding means an activity that mechanically reduces the size of
organic matter.
Composting Operations means an operation that is conducted for the purpose of
producing compost. Shall be by means of one or a combination of the following
processes used to produce a compost product: static pile, windrow pile, or aerated
static pile.
Ordinance 670
Page 19
Green Waste includes but is not limited to such organic material as yard
trimmings, plant waste, manure, untreated wood wastes, paper products, and natural
fiber products.
Hogged Materials means mill waste consisting mainly of hogged bark, but may
include a mixture of bark, chips, dust, or other by-product from trees and vegetation.
Mulching is the process by which mixed green waste is mechanically reduced in
size for the purpose of making compost.
Static Pile means a compo sting process that is similar to the aerated static pile,
except that the air source mayor may not be controlled.
Windrow Composting Process means the process in which compostable material
is placed in elongated piles. The piles or windrows are aerated and/or mechanically
turned on a periodic basis.
Wood chips means chips of various species produced or used in chipping and
grinding operations.
Section 1908.1.3 is added as follows:
1908.1.3 Permit Required. A permit shall be obtained from the fire department
prior to engaging in the operation and storing processed of wood chips, hogged
material, fines, compost and raw product in association with yard waste and similar
material recycling facilities. (See Appendix Chapter 1 section 105.6). The permit shall
be renewed on an annual basis, or shall be limited to such period of time as designated
by the Chief. Permits shall not be transferable and any change in use, location,
occupancy, operation or ownership shall require a new permit.
Section 1908.1.4 is added as follows;
1908.1.4 Security Bond/Financial Commitment for Cost Recovery. A security
bond or other approved form of financial commitment may be required by the Chief to
be posted, in an amount determined by the Chief, not less than $25,000.00, nor more
than $100,000.00, depending on the size of operation. The security bond or financial
commitment shall reimburse the fire department for expenses incurred in any
emergency response and/or enforcement action by the fire department to protect the
public from fire or hazardous substances related to the operation. The security
bond/financial commitment shall be returned to the operator in a timely fashion upon
satisfactory closure of the operation as determined by the Chief.
Ordinance 670
Page 20
Section 1908.2 is modified to read as follows:
1908.2 Storage Site. Storage sites shall be reasonably level and be solid ground
or other approved all-weather surface.
Section 1908.3 is modified to read as follows:
1908.3 Size of Piles. Pile height, width, and length shall be limited to criteria
approved by the Chief, based in part on the site material handling equipment. In no
case shall the piles exceed 12 feet in height, 100 feet in width, and 200 feet in length.
Section 1908.4 is modified to read as follows:
1908.4 Fire Access Roadway. A fire access roadway shall be provided to the
site and on-site as approved by the Chief. It shall have a minimum width based upon
site material handling equipment and an approved driving surface as approved by the
Chief. In no case shall the fire access roadway be less than 20 feet wide.
Section 1908.6 is modified to read as follows:
1908.6 Static Pile Protection. Interior pile temperatures shall be monitored and
recorded on a regular basis per the Operational Plan. Internal pile temperatures must
be taken at 2/3 the pile height, 12 to 24 inches from the surface with a probe-type
thermometer. Readings shall be made at not greater than 50-foot intervals along the
length of the pile.
Temperatures above 158 degrees F are known to adversely affect microbial
decomposition and are considered excessive. Infrared thermometers may be used to
monitor for hot spots at the surface, but are not a substitute for internal probe
measurement and documentation.
Once windrows exceed 170 degrees F, the windrows must be reduced in size, be
rotated and be monitored daily until temperatures drop below 158 degrees F. All green
waste stockpiles shall be re-mixed as necessary to alleviate any fire due to
spontaneous combustion or temperatures above 170 degrees F.
Windrows shall be visually inspected on a regular basis. Once fires have been
detected in any windrows at a site, this visual inspection shall be a minimum daily
requirement. Daily inspections shall continue until the threads of fire no longer exist,
and the Chief approves suspension.
All temperature and pile-handling records shall be kept on file at the site and be
made available for inspection by fire department personnel. Data shall include date,
time, temperature, specific location, and person conducting measurement.
Ordinance 670
Page 21
Section 1908.9 is modified to read as follows:
1908.9 Material Handling Equipment. Equipment used on all piles should be of
a type that minimizes compaction. All vehicles operating on or around the piles shall
have a Class A fire extinguisher of a minimum 2-A rating, in addition to the Class B
rating appropriate for the vehicles. Approved material-handling equipment shall be
available during fire fighting operations for moving wood chips, hogged material,
compost and raw product produced from yard waste and wood fines.
Section 1908.10.1 is added as follows:
1908.10.1 Operational and Emergency Plans. The following operational and
emergency action plans shall be submitted to and be approved by the Chief prior to
initiating operation:
1. Operational Plan. At a minimum the Operational Plan must include:
a) Site layout, pile dimensions, fire access, water supply, site security.
b) Site operations: temperature monitoring, rotation, diversion plan.
2. Emergency Plan. At a minimum the Emergency Plan must include:
a) Operator fire response actions, fire dispersal area, emergency
equipment operator callback, initiation of incoming diversion plan.
b) All plans shall define the equipment necessary to process and handle
the materials.
Section 1908.10.2 is added as follows:
1908.10.2 Notification of Fire. All fires shall be reported to the Fire Department
immediately upon discovery.
Section 1908.10.3 is added as follows:
1908.10.3 Equipment Operator Emergency Callback. The operator shall
implement and maintain a plan for rapid equipment operator response to the site. The
maximum response time to the site shall be within one hour of a fire department
notification. The following equipment shall be on site and staffed with skilled operators:
bulldozer, loaders and heavy duty equipment necessary to mitigate a fire. Notification
procedure shall be maintained operational 24 hours a day, seven days a week.
Notification may be by pager activation or telephone answering service or other
approved means.
Ordinance 670
Page 22
Section 1908.11 is added as follows:
1908.11 Combustible Vegetation Control. The operator shall clear any
combustible material, weeds, brush, trees or other vegetation (including mulch) that is,
or could become, dry and could be capable of transmitting fire, from within 50 feet of
raw green waste and mulch piles. Clearance shall be to bare earth or approved
pavement. Individual growing trees within that distance may remain with approval of the
Chief.
Section 1908.12 is added as follows:
Section 1908.12 Firefighting Water Supplies and Storage
1908.12.1 Public Water Supply. The operator shall provide and maintain
approved fire hydrants and waterline mains as required by the Chief. Water lines may
be approved aboveground lines supplied from a reliable water supply with adequate
protection against impact and fire flow reaction. Hydrant spacing shall be at 400-foot
intervals along primary fire access roadways. Fire flow at the hydrant(s) shall be least
1000 gallons per minute at 20 psi. Duration of the required fire flow shall be as
determined by the Chief.
1908.12.2 Private Water Supply. Above-ground water storage tanks may be
installed when authorized by the Chief where public water supply is not adequate to
meet fire flow requirements. Volume and duration of the required fire flow shall be as
determined by the Chief.
Section 1908.13 is added as follows:
1908.13 Site Equipment Maintenance - General Safety Rules. Welding or cutting
torch operations shall be conducted a minimum of 30 feet from combustible materials.
A fire watch shall be provided to detect fire, and to operate fire-extinguishing equipment
throughout the welding or cutting operation and 30 minutes thereafter. Refueling and
on-site maintenance shall meet the standards set forth in California Fire Code Chapter
22 and 34 - Flammable and Combustible Liquids, and all other applicable fire code
requirements.
Section 1908.14 is added as follows:
1908.14 Site Security. Pile storage areas shall be surrounded with approved
fencing. Fences shall be a minimum of 6 feet in height.
Ordinance 670
Page 23
Section 1908.15 is added as follows:
1908.15 Smoking and Open Burning Prohibited. The operator shall prohibit
smoking and open flame on the operational site, including smoking within vehicles.
Approved signs shall be clearly and prominently posted, and shall be enforced by the
site operators. No open burning will be allowed on site.
Section 1908.16 is added as follows:
1908.16 Incoming Waste Diversion Plan. The operator shall develop a diversion
plan for incoming green waste for implementation in the event of equipment failure or
other inability to process and distribute green waste. The plan shall prevent stockpiling
of waste on the site and unauthorized depositing of waste on or near the site. The
operator shall initiate the diversion based on criteria in the Operational and Emergency
Plan without further direction from the fire department.
Section 1908.17 is added as follows:
1908.17 Unprocessable or Non-Green Waste Material. All green waste that
cannot be processed on-site, such as stumps and fibrous plants, shall be immediately
removed from the feedstock, stored in roll-off containers or bins, and be removed from
the facility on a weekly basis. All plastic bags shall be removed prior to shredding
material.
15.24.110 General Fire Protection and Life Safety Requirements
Section 2306.2 is modified as follows:
Table 2306.2, Exception j is deleted.
15.24.120 Explosive Materials Storage and Handling
Section 3304 is added as follows:
3304 Explosives and Blasting Agents. The storage of explosives and blasting
agents is prohibited, and is hereby established as the jurisdictional limits of the City of
Poway.
Ordinance 670
Page 24
15.24.130 Building/Fire Code
Section 3404.2.9.5.1 is modified to read as follows:
3404.2.9.5.1 Location Where Above-ground Storage Tanks Are Prohibited. The
limits referred to in sections 3404.2.9.5.1 and 3406.2.4.4 of the 2007 California Fire
Code and the 2006 International Fire Code in which storage of flammable or
combustible liquids in outside above-ground tanks is prohibited are hereby established
as the jurisdictional limits of the City of Poway (see exceptions at section 3404.2.9.5.1).
Exceptions:
1. With the Chief's approval, Class I and II liquids may be stored above-ground
outside of buildings in specially designed, approved and listed containers which have
features incorporated into their design which mitigates concerns for exposure to heat,
ignition sources and mechanical damage. Containers must be installed and used in
accordance with their listing, and provisions must be made for leak and spill
containment. The Chief may disapprove the installation of such containers when in his
or her opinion their use presents a risk to life or property. Storage in such tanks on any
site shall not exceed five hundred fifty (550) gallons for Class I or one thousand one
hundred (1,100) Gallons of Class II liquids. In no case shall such storage be permitted
within one hundred (100) feet of any residential or institutional setting. Venting shall
meet Fire Code and Air Pollution Control District standards and "No Smoking" signs
shall be provided and the tank marked accordingly.
2. Crankcase draining may be stored in specially constructed above-ground
storage tanks, approved by the Chief, with a maximum capacity of 550 gallons. Such
tanks may be located within a building when the Chief deems appropriate, and the
container must be a specially designed, approved and listed container which has
features incorporated into its design which mitigate concerns for exposure to heat,
ignition sources and mechanical damage. Containers must be installed and used in
accordance with their listing, and provisions must be made for leak and spill
containment. In no case shall such storage be permitted in residential or institutional
property.
3. With the Chief's approval, temporary storage of a maximum of 10,000 gallons
Class II liquids may be permitted for a period not to exceed 90 days at remote
construction sites and earth moving projects consistent with sections 3404 and 3406.
4. The following criteria shall be applied in areas within the South Poway
Business Park, which are designated Commercial, Light Industrial, or Industrial Park.
With the Chief's approval, Class I and II liquids may be stored above-ground outside of
buildings in specially designed, approved, and listed containers which have features
incorporated into their design which mitigate concerns for exposure to heat (two-hour
Ordinance 670
Page 25
fire-resistance), ignition sources, and mechanical damage. Containers must be installed
and used in accordance with their listing, and provisions must be made for leak and spill
containment. Storage in such tanks on any site shall not exceed 5,000 gallons for Class
lor 10,000 gallons for Class II liquids. The Chief may disapprove the installation of such
containers when, in the Chief's opinion, their use presents a risk to life or property. In no
case shall such storage be permitted on residential or institutional property. A permit
shall be obtained from the Fire Department following the approval of submitted plans
prior to installation. Tanks shall be required to be secured by fencing and to have
appropriate signage. The City's Development Services Director shall determine
methods of visually screening these tanks. In no case shall such installation be
permitted within 50 feet of any building or property line which can be built upon,
including the opposite side of a public way, unless, an alternative design method for
such installation is approved by the Fire Department and by any other appropriate City
of Poway departments deemed necessary, including the City's Development Services
Department. Temporary above-ground tanks for storage of Class I liquids of a maximum
capacity of 550 gallons or Class II tanks with a maximum capacity of 10,000 gallons,
may be installed for a maximum of 90 days under specific restrictions and safeguards,
on remote, isolated, secured construction sites, earth moving projects, gravel pits or
borrow pits, when approved by the Chief.
Section 3405.2.4 is modified as follows:
3405.2.4 Class I, II, and III Liquids. Exception 4 is deleted.
15.24.140 Liquefied Petroleum Gases
Section 3807.5 is added as follows:
3807.5 Securing Tanks to Ground (Liquefied Petroleum Gases). Tanks shall be
secured to prevent the tank from rolling or moving when required by the FAHJ.
15.24.150 Appendix Chapter 1 - Administration
Section 102.10 is added to Appendix Chapter 1 as follows:
102.10 Repeal of Conflicting Ordinances, Resolutions or Motions. All former
ordinances, resolutions, or motions, or parts thereof, conflicting or inconsistent with the
provisions of this Ordinance or of the Code or standards hereby adopted are repealed.
Ordinance 670
Page 26
Section 103.2.1 of Appendix Chapter 1 is added as follows:
103.2.1. The Fire Code Official for the City of Poway shall be the following:
Wherever the term "Fire Code Official" is used in the California Fire Code, it
means "Fire Marshal". The Fire Marshal is authorized to exercise the powers and
perform the duties as set forth in this Code.
Section 104.12 of Appendix Chapter 1 is added as follows:
Section 104.12 Cost Recovery
Section 104.12.1 Purpose. The purpose of this section is to establish authority to
obtain reimbursement from responsible individuals for the expenses of any emergency
response and/or enforcement action by the City of Poway to protect the public from fire
or hazardous substances and situations.
Section 104.12.2 Reimbursement.
(a) In accordance with Health and Safety Code section 13000 et seq., an
individual who acts negligently or in violation of the law and thereby requires the
jurisdiction to provide an emergency response to a danger posed by a fire or hazardous
substance shall be liable for reimbursement to the agency for the costs incurred.
(b) In accordance with Government Code sections 53150 through 53158, any
individual who is under the influence of an alcoholic beverage, or any drug, or the
combined influence of an alcoholic beverage or any drug, and whose negligent
operation of a motor vehicle, boat or vessel, or civil aircraft caused by that influence,
proximately causes any incident and thereby requires the agency to provide an
emergency response shall reimburse the agency for the cost incurred.
Section 105.1.2 of Appendix Chapter 1 is modified to read as follows:
105.1.2 Permits. Permits as required by the Chief, are obtained from the Fire
Prevention Division. An application approved by the Chief and the payment of a permit
fee shall be required for such a permit. Such permit fees shall be established by
resolution of the City Council.
Ordinance 670
Page 27
Section 105.3.8 is added to Appendix Chapter 1 as follows:
105.3.8 Expense Recovery. The purpose of this section is to establish authority
to obtain reimbursement from responsible individuals for the expenses of any
emergency response and/or enforcement action by the City of Poway to protect the
public from fire or hazardous substances and situations. Such expense recovery fees
shall be established by resolution of the City Council.
Section 105.6.5.1 is added to Appendix Chapter 1 as follows:
105.6.5.1 Christmas Tree Lots. An operational permit is required to operate a
Christmas tree lot with or without flameproofing services.
Section 105.6.19.1 is added to Appendix Chapter 1 as follows:
105.6.19.1 Green Waste Recycling, Mulching, Composting Operations and
Storage. A Permit is required per section 1908.3 of Chapter 19.
Section 108 of Appendix Chapter 1 is deleted, and Section 15.24.160 is added in its
place as follows:
15.24.160 Appeals
15.24.160 Appeals. Whenever the Chief has denied a permit or other entitlement,
or when it is alleged that a mistake has been made in the interpretation or application of
the Code, the applicant may appeal the decision of the Chief to the City Manager by filing
a written appeal with the City Clerk within 30 days of the decision. If the appeal is denied
by the City Manager, the City Manager's decision may be appealed to the City Council by
filing a written appeal with the City Clerk within 30 days of the City Manager's decision.
Section 109.3 of Appendix Chapter 1 is modified to read as follows:
Appendix Chapter 1 Section 109.3 Penalties. It is unlawful for any person to
violate any of the provisions of this Code or standards hereby adopted by reference as
a part of this Code, or to fail to comply with any lawful order issued pursuant to this
Code, or to violate any permit or condition of approval issued pursuant to this Code. It
is further unlawful for any person to fail to comply with any lawful order issued pursuant
to this Code by the City Attorney or by a court of competent jurisdiction. A violation of
any provision of this Code, or failure to comply with orders or conditions issued pursuant
to this Code, shall constitute a misdemeanor, as set forth in Chapter 1.08 of the PMC,
and, in the alternative, shall be subject to civil and administrative penalties, as set forth
in Chapters 1.08 and 1.10 of the PMC.
Ordinance 670
Page 28
Section 111.4 of Appendix Chapter 1 is modified to read as follows:
111.4 Failure to Comply. It is unlawful for any person to continue any work after
having been served with a stop work order, except such work expressly identified in the
stop work order as necessary to correct a violation or unsafe condition.
15.24.170 Appendix B Fire-Flow Requirements For Buildings
Section B102.1 of Appendix B is modified to add a definition of Hazardous Fire
Area as follows:
Appendix B102.1 Hazardous Fire Area. Any geographic area mapped by the
State or local jurisdiction as a high, or very high fire hazard area, or as set forth by the
FAHJ that contains the type and condition of vegetation, topography, weather, and
structure density to potentially increase the possibility of vegetation conflagration fires
shall be considered a hazardous fire area.
Section B1 03.3 of Appendix B is modified to read as follows:
B103.3 Areas Without Water Supply Systems. For information regarding water
supplies for firefighting purposes in rural areas and suburban areas in which adequate
and reliable water supplies do not exist, the Fire Code Official is authorized to utilize
provisions in Appendix B of this Code or the standard published by the Insurance
Services Office document entitled "Guide for Determination of Required Fire Flow."
Section B106 of Appendix B is modified as follows:
B 106 Referenced Standards. The references to ICC IWUIC-06 and NFPA 1142-
01; and to the Fire Code portion of the California Building Standards Code in section
B106 of Appendix B, are hereby deleted.
15.24.180 Geographic Limits. The geographic limits referred to in certain
sections of the 2007 California Fire Code are hereby modified as follows:
Section 3204.3.1.1 is modified to read as follows:
3204.3.1.1 Outdoor Storage - Location. The geographic limit in which the
storage of flammable cryogenic fluids in stationary containers is prohibited is hereby
established for the City of Poway.
Ordinance 670
Page 29
Section 3406.2.4.4 is modified to read as follows:
3406.2.4.4 Locations Where Above-Ground Tanks Are Prohibited. The
geographic limits in which the storage of Class I and Class II liquids in above-ground
tanks is prohibited in residential areas is hereby established as jurisdiction limits of the
City of Poway.
Section 3804.2 is modified to read as follows:
3804.2 Maximum Capacity Within Established Limits. The geographic limits in
which the bulk storage of liquefied petroleum gas is prohibited for the protection of
heavily populated and congested areas is hereby established as jurisdiction limits of the
City of Poway except for areas specifically zoned by the City for such uses.
15.24.190 Conflict.
All other ordinances or parts of ordinances in conflict herewith are hereby
repealed. Wherever a conflict exists in this Code, the more restrictive requirement shall
apply.
SECTION 2. Upon passage, the City Clerk shall transmit a copy of this
Ordinance to the California Building Standards Commission pursuant to Health and
Safety Code section 17958.7, and the California Department of Housing and
Community Development.
SECTION 3: This Ordinance shall be codified.
EFFECTIVE DATE: This Ordinance shall take effect and be in force thirty (30)
days after the date of its passage; and before the expiration of fifteen (15) days after its
passage, it shall be published once with the names of members voting for and against
the same in the Poway News Chieftain, a newspaper of general circulation published in
the City of Poway.
Ordinance No. 670
Page., 30
Introduced and first read at a Regular Meeting of the City Council of the City of Poway
held the 13th day of November 2007, and thereafter PASSED AND ADOPTED at a
regular meeting of said City Council held the 27th day of November 2007.
or
~~~
L. Dian Shea, City Clerk'
STATE OF CALIFORNIA )
) ss
COUNTY OF SAN DIEGO )
I, L. Diane Shea, City Clerk of the City of Poway, do hereby certify under penalty
of perjury that the foregoing Ordinance No. 670 was duly adopted by the City Council at
a meeting of said City Council on the 27th day of November 2007, and that it was so
adopted by the following vote:
AYES: BOYACK, EMERY, HIGGINSON, REXFORD, CAFAGNA
NOES: NONE
ABSENT: NONE
DISQUALIFIED: NONE
L~'z?:~le'~
City of Poway